Info Produk
Allows you to measure insulation resistance more
safely by avoiding operation mistakes.
• Hot-line state ( 30V minimum) detection
• Large volt mark with the buzzer sound
• Automatic data hold function
• Bargraph just like analog meter
• Large display with backlight
• Easy to use & tough body
• Display: Numeral display 4000
• Sampling rate: 2 times/ sec.
• Safety: IEC 61010 CAT.III 600V
Measuring Ranges
Best Accuracy
Resolution
M©
4M/ 40M/ 400M/ 4000M
± ( 3% + 4)
0, 01M©
Test Voltage
1000V/ 500V/ 250V
ACV/ DCV
600V ( AC/ DC Automatic dedection)
± ( 3% + 2)
1V
©
4000© ( Buzzer and Alarm)
± ( 3% + 3)
1©
©
40©
± ( 3% + 10)
1©
Open circuit Voltage
1 to 1, 3 times of nominal test voltage
Rated measurement current
1, 0~ 1, 2 mA
Short circuit current
2 mA or less
Live circuit detection
At e 30V AC/ DC or more, inhibits test.buzzer sound and Alarm indicator lights up.
Battery
LR 6x6
Size/ Weight
H170xW142xD57mm / 600 gr.
Standard Accessories
Test Lead ( TL-112) , Strap ( ST-50) , Instruction Manual
OPTIONAL ACCESSORIES
Clip Adapter: CL-16
Test Lead: TLF-120 ( MG 500 and MG 125 only)